Quadri elettrici e apparecchiature

MV Switchgear and Components

For Industry

Product by

Medium Voltage (MV) switchgear and equipment, manufactured by IME Quadri of the Col Group, represent the core of industrial electrical distribution systems, ensuring control, protection, and service continuity. Designed to guarantee maximum safety and reliability, MV switchgear adapts to various plant configurations, integrating advanced devices for operation, measurement, and line protection. Each solution is developed according to the strictest technical and regulatory standards, providing long-lasting performance even in the most complex and critical environments.

Normoclad MV Switchgear

up to 36 kV – up to 4000 A – up to 50 kA

Normoclad is the family of air-insulated MV switchgear designed for primary distribution.
Previously referred to as “shielded,” they are now classified as LSC2B-PM according to service continuity loss definitions.
Normoclad MV switchgear up to 24 kV is available in the IAC AFLR version with internal arc resistance on all four sides, in compliance with IEC 62271-200 standards.

MINIBLOC-6 MV Switchgear

up to 24 kV – 400÷1250 A – 25 kA

Minibloc-6 is the family of air-insulated MV switchgear designed for secondary distribution.
Previously referred to as “protected,” they are now classified as LSC2A-PM according to service continuity loss definitions.

Minibloc-6 MV switchgear is available in the IAC AFLR version with internal arc resistance on three sides (front, side, rear; 21 kA for 1″), in compliance with IEC 62271-200 standards.

MINIBLOC AIR MV Switchgear

up to 24 kV – 400÷1250 A – 25 kA

Minibloc Air, the evolution of our Minibloc-6, is the new switchgear dedicated to secondary MV distribution, insulated in an SF₆-free gas mixture to ensure minimal environmental impact.
With a rated voltage up to 24 kV, it falls within the LSC2A-PM classification according to service continuity loss definitions, and is available in an internal arc-resistant version in compliance with IEC 62271-200 standards.

MINIBLOC-636 MV Switchgear

36 kV – 630 A – 20 kA

Minibloc-636 is the family of air-insulated MV switchgear designed for secondary distribution.
Previously referred to as “protected,” they are now classified as LSC2A-PM according to service continuity loss definitions.

Minibloc-636 MV switchgear is available in the IAC AFLR version with internal arc resistance on all four sides, in compliance with IEC 62271-200 standards.

ROTOBLOC MV Switchgear

up to 24 kV – 400÷1250 A – 20 kA

Rotobloc is the family of air-insulated MV switchgear designed for secondary distribution.
Previously referred to as “protected,” they are now classified as LSC2A-PI according to service continuity loss definitions.
They can be equipped with air-insulated IMS modules.

Sinter Equipment

24 kV – 630 A – up to 16 kA

The multifunctional SINTER device, designed for Minibloc-6 MV switchgear, combines the functions of switching and disconnection in a single SF₆-insulated unit. Thanks to this solution, the switchgear is about one-third more compact than a traditional configuration (where circuit breaker and disconnector are two separate devices), while remaining fully equivalent from a functional standpoint.

Sinter Air Equipment

24 kV – 630 A – up to 16 kA

The multifunctional SINTER device, designed for Minibloc Air switchgear, combines the functions of switching and disconnection in a single SF₆- Free gas – insulated unit. Thanks to this solution, the switchgear is about one-third more compact than a traditional configuration (where circuit breaker and disconnector are two separate devices), while remaining fully equivalent from a functional standpoint.

RI and SRI Air-Insulated Rotary Load Break Switch–Disconnector

24 kV – 400 A – 16 kA

The RI air-insulated load break switch is designed for easy installation in MV compartments with a front width of 700 mm, and it simplifies maintenance operations since the complete device can be easily removed from the compartment and its control unit is removable. Opening and closing operations are independent of the operator.

SCR-SGV Hinge-Type Load Break Switch–Disconnector

up to 36 kV – up to 630 A – 16 kA

The SCR/SGV hinge-type load break switch–disconnector features arc extinction achieved through air blowing generated by three independent cylinders with self-blowing pistons, one for each phase, aligned with the poles. It is also available in a motorized version and is approved according to ENEL DY515 and DY516 standards.

SDL Hinge Disconnector

up to 36 kV – up to 2500 A – 50 kA

The SDL hinge disconnector is designed for wall-mounted installation but can also be used in MV switchgear and secondary substations. The standard three-pole version is intended for vertical installation. Bipolar and unipolar versions are available upon request. It is maintenance-free.